PROFINET Overview
PROFINET is industrial Ethernet. The controller finds the field device by its station name, and once it is configured with the device description file (GSDML), the two sides exchange process data cyclically.
You don't have to read the spec first. Three things are enough: find the device by station name, configure with the GSDML, you are only connected once cyclic exchange starts.
The Darra Profinet Slave is PROFINET IO Device, real-time level RT Class 1 (IRT is not supported). Connect it to an IO controller and use it like this:
- Write Q: Equipment → Controller
- Read I: Controller → Device
This product stands on the device side: it does not actively scan for other devices on the network, and it does not establish application relationships on its own. A value being present does not mean it is usable in this cycle.
What steps are involved in a single connection?
- Configure the device ID, process data length, and network interface in the configuration tool.
- Export the GSDML, then import it into TIA's hardware catalog
- Assign the station name for this unit — it must match the station name in the configuration tool
- Compile and download to the PLC in TIA; start the service in the configuration tool
- Both sides enter cyclic exchange — only then is it connected
The first few steps are all preparation. Only in cyclic exchange is the controller really exchanging process data — a device that has started, or that is visible on the network, is not the same as connected.
In Favor and Opposed
Only follow the instructions in the table below. Do not use these settings to configure projects not listed in the table.
Support:
| Item | Note |
|---|---|
| RT Class 1 cyclic IO | The cycle is configured in the configuration tool / by the controller, minimum 1 ms; the protocol sends frames per the configuration, the application does not push frames |
| One fixed process data module | Only slot 1 / subslot 1 — that one module: the type is not selectable, and it cannot be added or removed. The byte count is configured in the configuration tool |
| IOPS / IOCS and DataStatus | Each cycle's data carries quality flags; it is not WKC |
| AR establishment and release | Initiated by the controller; cyclic exchange starts once the GSDML configuration is agreed |
| DCP | Identify, set station name, set IP, restore factory settings. Signal light requests are logged only; no actual flashing occurs; no DHCP |
| LLDP | Send Only + Limited Receive (One Neighbor Per Port) |
| Record read/write | Includes I&M0–I&M3 |
| Diagnostics | Qualified USI 0x8003 |
| Alarms | Only received and acknowledged, never sent proactively |
| SNMP | Read-only, all network interfaces UDP 161: MIB-II system group + ifTable. Only Get / GetNext are supported — see the note below |
| GSDML export | Generated on the fly via "Export" in the configuration tool; no ready-made file ships with the installation package |
- Only Get / GetNext are supported. It does not accept GETBULK, so
snmpwalkwith default parameters will get no response at all — when troubleshooting, specify GET/GetNext explicitly, and do not take "walk gets nothing" to mean SNMP is off. - It is a service-layer function: with
DarraPnSServicestopped, there is no SNMP. - Conversely, even when the stack is idle or unauthorized, it still responds—the fact that system information can be read does not mean the device has entered a cyclic exchange.
- Sending a GET to PROFINET's IIM / IDM MIB (
1.3.6.1.4.1.4329.*) will return noSuchName as-is (nothing is registered there); that is not a bug. - No "remote neighbor" row: LLDP-MIB Only local tables are available; remote neighbors cannot be read.
- Writing
SupportedProtocols="LLDP"/SupportedMibs="MIB2"in the GSDML is not an SNMP declaration to the controller; do not treat it as one.
Not supported:
| Item | Note |
|---|---|
| RT Class 2 / RT Class 3 (IRT) | Rejected during the connection phase based on the IRT configuration |
| RT_CLASS_UDP, Isochronous Mode | Not doing it |
| Clock Synchronization | PTCP / PTP / 1588 / SNTP / NTP None at all |
| MRP / MRPD | Do not implement ring network redundancy |
| Shared Device, iDevice, Controller Role | This product is designed exclusively for the device side. |
| Substitution | There is only one global fill byte |
| iPar / Parameter Server | Not doing it |
| PROFINET Security | Not doing it |
| HTTP API Authentication | Perform only a loopback source check, not authentication |
| PI conformance certification | The GSDML declares Conformance Class A; no PI certification test has been performed |
Some fields in the exported file are filled in to satisfy the engineering software (the structure follows a Siemens sample project) and cannot be taken as evidence that "this device supports some feature" — for example, declarative fields about clock synchronization appearing in the file does not mean PTCP is available.