PROFINET Overview

PROFINET is industrial Ethernet. The controller finds the field device by its station name, and once it is configured with the device description file (GSDML), the two sides exchange process data cyclically.

Basics for Beginners

You don't have to read the spec first. Three things are enough: find the device by station name, configure with the GSDML, you are only connected once cyclic exchange starts.

The Darra Profinet Slave is PROFINET IO Device, real-time level RT Class 1 (IRT is not supported). Connect it to an IO controller and use it like this:

  • Write Q: Equipment → Controller
  • Read I: Controller → Device

This product stands on the device side: it does not actively scan for other devices on the network, and it does not establish application relationships on its own. A value being present does not mean it is usable in this cycle.

What steps are involved in a single connection?​

  1. Configure the device ID, process data length, and network interface in the configuration tool.
  2. Export the GSDML, then import it into TIA's hardware catalog
  3. Assign the station name for this unit — it must match the station name in the configuration tool
  4. Compile and download to the PLC in TIA; start the service in the configuration tool
  5. Both sides enter cyclic exchange — only then is it connected

The first few steps are all preparation. Only in cyclic exchange is the controller really exchanging process data — a device that has started, or that is visible on the network, is not the same as connected.

In Favor and Opposed​

Only follow the instructions in the table below. Do not use these settings to configure projects not listed in the table.

Support:

ItemNote
RT Class 1 cyclic IOThe cycle is configured in the configuration tool / by the controller, minimum 1 ms; the protocol sends frames per the configuration, the application does not push frames
One fixed process data moduleOnly slot 1 / subslot 1 — that one module: the type is not selectable, and it cannot be added or removed. The byte count is configured in the configuration tool
IOPS / IOCS and DataStatusEach cycle's data carries quality flags; it is not WKC
AR establishment and releaseInitiated by the controller; cyclic exchange starts once the GSDML configuration is agreed
DCPIdentify, set station name, set IP, restore factory settings. Signal light requests are logged only; no actual flashing occurs; no DHCP
LLDPSend Only + Limited Receive (One Neighbor Per Port)
Record read/writeIncludes I&M0–I&M3
DiagnosticsQualified USI 0x8003
AlarmsOnly received and acknowledged, never sent proactively
SNMPRead-only, all network interfaces UDP 161: MIB-II system group + ifTable. Only Get / GetNext are supported — see the note below
GSDML exportGenerated on the fly via "Export" in the configuration tool; no ready-made file ships with the installation package
A few honest words about SNMP
  • Only Get / GetNext are supported. It does not accept GETBULK, so snmpwalk with default parameters will get no response at all — when troubleshooting, specify GET/GetNext explicitly, and do not take "walk gets nothing" to mean SNMP is off.
  • It is a service-layer function: with DarraPnSService stopped, there is no SNMP.
  • Conversely, even when the stack is idle or unauthorized, it still responds—the fact that system information can be read does not mean the device has entered a cyclic exchange.
  • Sending a GET to PROFINET's IIM / IDM MIB (1.3.6.1.4.1.4329.*) will return noSuchName as-is (nothing is registered there); that is not a bug.
  • No "remote neighbor" row: LLDP-MIB Only local tables are available; remote neighbors cannot be read.
  • Writing SupportedProtocols="LLDP" / SupportedMibs="MIB2" in the GSDML is not an SNMP declaration to the controller; do not treat it as one.

Not supported:

ItemNote
RT Class 2 / RT Class 3 (IRT)Rejected during the connection phase based on the IRT configuration
RT_CLASS_UDP, Isochronous ModeNot doing it
Clock SynchronizationPTCP / PTP / 1588 / SNTP / NTP None at all
MRP / MRPDDo not implement ring network redundancy
Shared Device, iDevice, Controller RoleThis product is designed exclusively for the device side.
SubstitutionThere is only one global fill byte
iPar / Parameter ServerNot doing it
PROFINET SecurityNot doing it
HTTP API AuthenticationPerform only a loopback source check, not authentication
PI conformance certificationThe GSDML declares Conformance Class A; no PI certification test has been performed
The exported file is not GSDML a list of features.

Some fields in the exported file are filled in to satisfy the engineering software (the structure follows a Siemens sample project) and cannot be taken as evidence that "this device supports some feature" — for example, declarative fields about clock synchronization appearing in the file does not mean PTCP is available.