GSD Documents

Beginner's Guide

GSD (called GSDML in PROFINET) = the device's "manual". Without this document in TIA, the device will not appear in the hardware catalog and cannot be dragged into the network.

The file tells the engineering software: what this piece of equipment is called, what modules it has, and how long the process data is.

After configuring the device in the configuration tool, export it, then add it in TIA under "Options → Manage GSD files". After changing the configuration, export again; the controller and the device use the same file.

I/Q is a matter of perspective: whichever side you stand on, Q is that side's output. This product is an IO module, so it writes its own Q (module output → IO controller) and reads its own I (IO controller output → module input). The IO controller also has its own I/Q, and each side's output matches the other side's input.

What it covers, what it doesn't cover​

PipeRegardless
Product type name (the model shown in the hardware catalog)This unit's station name on site
Module structure and process data lengthThis unit's IP on site
Order Number, Manufacturer InformationProgram on the Controller Side

The station name and IP are the runtime identity of this unit, assigned on the TIA side. They are not present in the GSDML.

The vendor / device ID is currently filled with a placeholder value (waiting for PI to allocate), so do not treat it as a stable product identifier in your code — to identify a device, go by the station name.

This is the only process data module that can be configured in the configuration.

Where is it from?​

After configuring the device in the configuration tool, export it:

  • "Export" in the top bar, or "Export XML" on the "XML preview" page
  • If the module structure or the process data length changed, re-export and import it into TIA again — the lengths in the old file will not match, and the application relationship cannot be established.

The export result feeds both sides at once: TIA uses it to recognize this device, and the server-side configuration uses it to align on the same set of parameters.

Import into TIA​

  1. In TIA, go to "Options" → "Manage GSD files" → add the exported GSDML
  2. Find it in the hardware catalog: Other field devices → Other Ethernet devices → PROFINET IO → I/O → Darra → PROFINET IO Device → Darra Profinet Slave
  3. Drag it into the network view, and configure the station name, cycle, and process data length.

The configuration must be consistent on both sides.​

Controllers and devices must be configured according to the same configuration file; if they do not match, the application cannot be established:

  • After changing the configuration on the device side, re-export and import it into TIA again; both sides use the same file.
  • The module structure and process data length must match on both sides.
  • Make configuration changes only while not in cyclic exchange.
Do not edit the file by hand

GSDML is generated by the configuration tool. Do not edit the protocol internals inside it by hand — the changes will not match, and they will be overwritten on the next export. Make any change in the configuration tool, then export again.