Discover and Connect
The controller doesn't IP connect to devices based on what you enter in the program. It first connects on the data-link layer Find Equipment by Station Name, Once the configuration is finalized, the system finally enters cyclic exchange. The connection is not established until cyclic exchange begins.
Process
| Stage | What happened? |
|---|---|
| Discovery | When the controller or engineering station queries the station name on the link, the device responds. |
| Set Parameters | Assign or confirm the station name IP(must GSDML match the configuration tool /) |
| Application Relationships | Verify the slot assignments and process data based on the configuration GSDML , and agree on the cycle. |
| Cycle Exchange | Both parties exchange process data at regular intervals. Only then is the connection established. |
| Release | The controller is actively released, or the device is disconnected after a watchdog timeout. The device returns to the "Ready to Connect" state. |
The application does not assemble these frames itself; it simply checks the result: whether or not it has entered the cyclic swap.
The station name is even IP more important than
For PROFINET Equipment Name Identification station.IP It can then be assigned by the controller.
- The site name in the configuration tool = the device name assigned TIA in [...].
- When there's a mismatch, the device is visible online, but an application relationship cannot be established.
When is it considered connected?
| Observation | Meaning |
|---|---|
| The device has been started | Listening to the controller, not the same as connected |
| Enter Cycle Exchange | Data is currently being exchanged with the IO controller |
| Configuration Error / Network Card Unavailable | First, check the device status and online TIA diagnostics, then make an educated guess about the process data. |
Do not disconnect the device while it is connected.
If the controller stops the equipment, resets it, or reloads its configuration during a cycle switch, the controller will lose the station connection and the diagnostic screen will flash.
- Still updating process data → Don't stop, don't reset, don't change the configuration
- Wait until the connection is disconnected before stopping or changing the configuration
- Once it stops, it stays stopped; it won't pull itself up on its own.
Writing process data is not subject to this restriction.