Equipment Model
TIA : What You See in Hardware Configuration Isn't a Flat Plate, but Rather Equipment → Tank → Submodule. Slot 0 is the device itself; process data is in the subsequent slots.
Tree Structure
IO Device
├── Slot 0 DAP (device itself, not removable)
└── Slot 1 process data module
| Level | Meaning |
|---|---|
| Equipment | One station name, one set IP, one PROFINET port |
| Slot | Module slots. Slot 0 is reserved for the main unit. |
| Submodule | Channels or process data blocks in the slot |
GSDML Specify which slots are allowed to contain what. If the configuration does not match, the application relationship cannot be established.
DAP
DAP (Device Access Point) Refers to the device itself:
- Always in Slot 0
- Does not carry user process data
- Device identifiers and interfaces
- Cannot be deleted from the configuration
Process data is available in Tank 1 and beyond.
The process area of this product
The process area of this product is located in Slot 1 / Sub-slot 1. The number of bytes is configured using the configuration tool and written to GSDML. Typical examples include Q (device → controller) at 20 bytes and I (controller → device) at 32 bytes, though these are not the only possible sizes. Do not add or remove slots on your own.
The 20-byte Input in the GSDML (device → controller) is the SDK's Q (Out / ProcessData.Out[i], the write direction); the 32-byte Output (controller → device) is the SDK's I (In / ProcessData.In[i], the read direction, read-only).
Configurations must be consistent
- This product is a fixed-size IO device with no optional modules.TIA Do not add or remove slots or submodules.
- After making changes, you'll need to re-export the file; use the same copy for both the controller and the device.
- Configuration changes must be made when the system is not in a cycle swap.