Diagnosis
This product is software IO Device; it has no on-site terminals. On a daily basis, first check whether it is connected and whether the data from this data point is usable; do not proactively report channel faults to the controller.
Connect
First, verify that you have entered cycle switching mode, then access the process data.
While the process data is still being updated, do not shut down the equipment or change the configuration.
Is the data valid?
Just because the value is still there doesn't mean this shot is usable. After a cable break, the old bytes may still be present, and the validity flag will change to "unusable."
Channel Diagnostics and Process Alarms
There are no on-site channels and no sensors. If the modules do not match, the protocol will handle it automatically; do not manually report a channel failure.
When channel diagnostics or process alarms are sent to the controller, they enter the PLC diagnostic buffer, which may cause the scan to stop. By substitution value, do not send.
Equipment Identification (I&M)
The controller can read the device identity:
- I&M0: Manufacturing Information (Manufacturer, order number, Serial Number, Version)
- I&M1–I&M3: Labels, locations, dates, and descriptions entered on-site (only displayed if entered via the controller; otherwise, the factory default values are displayed)
- I&M4: Not enabled
Station names and product names are based on the configuration tool and match the order numbers in the identification.
Watchdog and Site Downtime
| Event | Behavior |
|---|---|
| Received a controller cyclic frame | Refresh Watchdog |
| Watchdog Timeout | The link was disconnected according to protocol; the controller diagnosed a station loss. |
| The device did not output a valid Q | If a bid is deemed invalid, the link may not be immediately disconnected. |
After a site drop, the device returns to the "Ready to Connect" ST. Once the controller has reconfigured and reestablished the link, it resumes periodic exchange.
A watchdog timeout is a protocol-defined behavior, not an active alarm triggered by the application. Do not restart the device while the controller still considers it to be online.
Troubleshooting Procedure
- Is the equipment RUN? Are there any configuration errors?
- Has the cycle swap begun?
- Is this shot's data valid?
- Finally, the process data content